      Electrical fire monitor(LoRa)

      • Product introduction

      The combined electrical fire monitoring detector is based on the electrical fire monitoring system. In combination with the Internet of Things, real-time data monitored will be uploaded to the cloud platform in a timely and effective manner through new generation information technologies such as big data and cloud computing. The platform monitors, counts, analyzes and shares information on the collected data. This combined electrical fire monitoring detector mainly monitors residual current, over-current, temperature, voltage, arc, etc.

      • Details
      • The combined electrical fire monitoring detector is based on the electrical fire monitoring system. In combination with the Internet of Things, real-time data monitored will be uploaded to the cloud platform in a timely and effective manner through new generation information technologies such as big data and cloud computing. The platform monitors, counts, analyzes and shares information on the collected data. This combined electrical fire monitoring detector mainly monitors residual current, over-current, temperature, voltage, arc, etc.


        Main parameters of the product

        Monitoring equipment

        Heartbeat cycle

        The default is once every 10 minutes.

        Temperature test range

        0~150℃

        Residual current

        0~1000mA

        three-phase voltage

        100~500V

        three-phase current

        0~100A,3000:1 open close type transformer

        Detection channel

        Two circuit residual current detection, three circuit temperature detection

        Communication mode

        Frequency band

        CN470

        Uplink communication mode

        LoRa modulation

        Downlink communication mode

        Multi wire system

        Communication protocol

         

        LoRaWAN

        Input port

         

        Two residual currents/temperatures, three temperatures,one three-phase voltage channel and one three-phase current channel; 220V terminal blocks; 485 communication port.

        Output port

        Switch output port

        Empty transport distance

        485 communication < 500m

           Physical environment

        Working voltage

        220V

        Power consumption

        < 3W

         

         

         

        Others

        Adjustment accuracy (temperature and current)

        1℃,1mA

        Alarm loudness

        Not less than 70dB at 1m

        Working temperature

        (-10~60)℃

        Operating humidity

        (10~93)%RH

        Installation method

        Standard guide rail type, screw fixed installation

        IP protection grade

        IP30


      109